According to UL 489, a circuit breaker, must not trip at 100% of its current rating, a 20 amp breaker will hold 20 A forever. At 135%. It must trip within one hour for circuit breakers rated 50 A or less and at 200% it must trip within two minutes if rated 30 A or less.
Something gotta be wrong with 20 breaker failing to trip at 24 amps
I did not know that there was a curve and slightly exceeding the threshold would not cause it to trip immediately